Working voltage:DC8V~36V Continuous
-
Power consumption:Standby:24V:MAX 1W, Working:24V:MAX 5W
-
Rotate speed sensor Frequency:50-9000Hz
-
MAX Accumulating Time:99999.9Hours(Min Store time:6min)
-
Fuel Relay Output:5Amp DC+VE Supply voltage
MEBAY Genset Controllers for Generator Sets in Bangladesh
This Mebay controller specialized controller is designed for starting, stopping, and monitoring parameters and faults of Diesel/Gasoline/Gas Gensets. Featuring a 3-inch LCD screen, it displays multiple faults simultaneously, prompting shutdown if smooth operation isn't possible. It offers Chinese/English interfaces with additional languages available upon request. Parameters can be configured via front-facing buttons or programmable interfaces (USB/RS485) for PC adjustments. Ideal for various genset auto control systems.
Specifications:
Options |
Parameters |
Working voltage |
DC8V~36V Continuous |
Power consumption |
Standby:24V:MAX 1W |
Working:24V:MAX 5W |
|
AC Voltage Input |
1P2W 50VAC-276VAC(ph-N) |
2P3W 50VAC-276VAC(ph-N) |
|
3P4W 50VAC-276VAC(ph-N) |
|
Rotate speed sensor Frequency |
50-9000Hz |
MAX Accumulating Time |
99999.9Hours(Min
Store time:6min) |
Fuel Relay Output |
5Amp DC+VE Supply voltage |
Start Relay Output |
5Amp DC+VE Supply voltage |
Programmable Relay output 1 |
5Amp DC+VE Supply voltage |
Programmable Relay output 2 |
5AMP Non-contact-Normal
open--Normal close output |
Programmable Relay output 3 |
5AMP Non-contact Normal Open output |
Programmable Relay output 4 |
5AMP Non-contact normal open output |
Excitation output |
Max 1AMP DC+VE supply voltage |
Switch value input |
Available if connecting with
Battery - |
Working condition |
-25-65℃ |
Storage condition |
-40-85℃ |
Protection Level |
IP65:when waterproof rubber gasket is
added between controller and its panel |
Overall dimension |
189mm×134mm×50mm |
Panel cutout |
160mm×120mm |
Weight |
0.68Kg |
Features
There are four Models under DC4xD MK3 series.
DC40D MK3: used for single machine automation.
Start/Stop through remote start signal.
DC42D MK3:Based on DC40D, it adds Mains monitoring and
AMF (Mains/Generator automatic switching control ) , especially suitable for
the automation system composed by mains and genset.
DC40DR MK3:Based on DC40D, it adds RS485 communication port.
DC42DR MK3:Based on DC42D, it adds RS485 communication port.
DC42DR-ABF MK3:Based on DC42DR, it adds ABF backup battery pack measurement
and control function.
Main Features
32 units Micro-procession technology is used.
3 inches 128*64 LCD display with backlight, option
language interface(Chinese/English), user’s language set if necessary.
Control Protection: Auto Start/Stop of genset, load
transfer (ATS control) and perfect failure display and protection.
Various of crank conditions (RPM, Frequency, Oil
Pressure) can be chosen
Gather and display various engine and generator’s
parameters. Adapt to 3P4W,1P2W,2P3W (120V/240V,50/60HZ)
Sensor can be self-defined by front face button or PC
software.
With RS485 communication port, can achieve “Three Remote”
functions via MODBUS protocol.
Input/output function, status can be shown directly.
More categories of surface setting.
Real time clock inside: preset time operate and auto
maintenance is available. Genset working plan can be set as per week or month.
Countdown function, which can set the maintenance time
or date.
Records function: relative faults shall be recorded in
real time.
Totally 6 relay’s output, among which 4 relay output
can be self-configurable, each relay can be set as max 20 functions, besides,
there are 4 groups as non-contact terminals.
5 relays can be set as switch value input, and each
can be set as max 10 functions.
3 sensor simulation input connectors, 5 input types is
configurable and various kinds of units can be set.
Standard water-proof rubber gasket. The waterproof can
reach IP65.
Module design: All the connections are adapted with
European connectors so that installation, connection, repair and replacement
can be more easily.
Parameters Display
Engine RPM
Engine oil pressure
Engine water temperature
Engine oil temperature
Engine cylinder temperature
Engine fuel level
Engine battery voltage
charging voltage
Mains Frequency (only for DC42D/DC42DR)
Mains phase voltage L-N(only for DC42D/DC42DR)
Mains phase voltage L-L(only for DC42D/DC42DR)
Generator 3 Phase voltage L-N
Generator 3 Phase voltage L-L
Generator 3 phase current A
Generator Frequency Hz
Generator Power Factor COSφ
Generator active power KW
Generator apparent power KVA
Generator reactive power KVar
Current consumption Kwh
Total consumption Kwh
Total Crank times
Current running time
Total running time
Maintenance notice
Current date / time
Protection
over speed
under speed
Low oil pressure
High water temperature
High Oil temperature
High Cylinder Temperature
Low fuel level
Low oil level
External emergency alarm
RPM Lost
Sensor Open
Over Frequency
Under Frequency
Over voltage
under voltage
over current
Non-balance of current
Over power
Lack of Phase
Maintenance expire ECU
ECU alarm failure
ECU communication Failure
Low water level alarm
Emergency Stop
Crank failure
Over battery voltage
Under Battery voltage
Charging failure
Stop Failure