Full Specification of AP 15 Diesel Generator With Details Guide!
- Product: PERKINS
- Alternator: ECP 3-2L/4 C
- CONTROL SYSTEM: DSE 6120
Aksa power generation system, providing optimum performance, and reliability, for stationary standby, prime power, and continuous duty applications. All generator sets are factory build, and production tested.
Certificate
- TS ISO 8528
- TS ISO 9001-2008
- CE
- SZUTEST
- 2000/14/EC
General Characteristics
Model Name | AP 15 |
Frequency (Hz) | 50 |
Fuel Type | Diesel |
Engine Made and Model | PERKINS - 403A-15G1 |
Alternator Made and Model | Mecc Alte - ECP 3-2L/4 C |
Control Panel Model | DSE 6120 |
Canopy | AK 10 |
3 Phase, 50 Hz, PF 0.8
VOLTAGE | STANDBY RATING (ESP) | PRIME RATING (PRP) | Standby Amper | ||
kVA | kW | kVA | kW | ||
400/231 | 14.5 | 11.60 | 13 | 10.40 | 20.93 |
STANDBY RATING (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528-1. Overload is not allowed.
PRIME RATING (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation.
ENGINE SPECIFICATIONS
Engine | PERKINS | |
Engine Model | 403A-15G1 | |
NO. OF CYLINDERS AND BUILD | 3 cylinders - in line | |
BORE AND STROKE | mm | 84 X 90 |
TOTAL DISPLACEMENT | L | 1.496 |
Aspiration | Naturally Aspirated | |
COMPRESSION RATIO | 22.5:1 | |
RATED SPEED (RPM) | d/dk | 1500 |
OIL CAPACITY | L | 6.0 |
Standby Power (kW/HP) | 13.5/18.09 | |
Prime Power | 12.2/16.35 | |
Block Heater QTY | 1 | |
Block Heater Power (Watt) | 250 | |
Fuel Type | Diesel | |
Injection Type and System | Indirect | |
Type of Fuel Pump | Zexel Cassette type - In-Line | |
Governor System | Mechanic | |
Operating Voltage (Vdc) | 12 Vdc | |
Battery and Capacity (Qty/Ah) | 1x36 | |
Charge Alternator (A) | 15 | |
Cooling Method | Water Cooled | |
Cooling Fan Air Flow (m3/min) | 36.6 | |
Coolant Capacity (engine only / with radiator) (lt) | 2.6/6.0 | |
Air Filter | Dry Type | |
Fuel Cons. Prime With %100 Load (lt/hr) | 3.67 | |
Fuel Cons. Prime With %75 Load (lt/hr) | 2.79 | |
Fuel Cons. Prime With %50 Load (lt/hr) | 2.04 | |
ALTERNATOR SPECIFICATIONS
Manufacturer | Mecc Alte | |
Alternator Made and Model | ECP 3-2L/4 C | |
Frequency (Hz) | Hz | 50 |
Power (kVA) | kVA | 13.5 |
DESIGN | Brushless | |
VOLTAGE | V | 400 |
Phase | 3 | |
A.V.R. | DSR | |
Voltage Regulation | (+/-) | 1 |
Insulation System | H | |
Protection | IP23 | |
Rated Power Factor | 0.8 | |
WEIGHT COMP. GENERATOR (Kg) | 87 | |
COOLING AIR (m³/min) | m3 | 3 |
SIZE and WEIGHT
Open Type | DRY WEIGHT (kg.) | LENGTH | WIDTH | HEIGHT | TANK CAPACITY (lt.) (Lt.) |
425 | 1265 | 850 | 1067 | 50 | |
CANOPY | DRY WEIGHT (kg.) | LENGTH | WIDTH | HEIGHT | TANK CAPACITY (lt.) (Lt.) |
AK 10 | 565 | 1851 | 910 | 1181 | 50 |
STANDARD SPECIFICATIONS
Water cooled, Diesel engine
Radiator with mechanical fan
Protective grille for rotating and hot parts
Electric starter and charge alternator
Starting battery (with lead acid) including rack and cables
Engine coolant heater
Base frame design incorporates an integral fuel tank and anti-vibration isolators
Flexible fuel connection hoses
Single bearing, class H alternator
Industrial exhaust silencer and steel bellows supplied separately(for open sets)
Static battery charger
Manual for application and installation
OPTIONAL EQUIPMENTS
ENGINE
• Fuel-Water Seperator Filter• Low water level alarm
• Oil heater
ALTERNATOR
• Anti-Condensation Heater• Over sized alternator
• Main line circuit breaker
CONTROL SYSTEM
• Remote annunciator panel• Remote relay output
• Alarm output relays
• Remote communication with modem
• Earth fault, single set
• Charge Ammeter
TRANSFER SWITCH
• Three or four pole contactor• Three or four pole motor operated circuit breaker
OTHER ACCESSORIES
• Main Fuel Tank• Automatic or manual fuel filling system
• Manual oil drain pump
• Residential silencer
• Enclosure: weater protective or sound attenuated
• Duct adapter ( on radiator)
• Inlet and outlet motorised louvers
• Inlet and outlet acoustic baffles
• Trailer
• Tool kit for maintenance
• Supplied with oil and coolant - 30 °C
• Battery isolating switch
AP15 Diesel Generator: Power Packed in a Compact Package
In the modern world, where consistent power is crucial for a multitude of applications, the AP15 Diesel Generator by [Your Company], with its compact yet robust 15 KVA capacity, emerges as a versatile and reliable source of electricity. In this comprehensive blog, we will delve into various aspects of the AP15, from its key features to applications and maintenance tips.
Key Features
- Compact Powerhouse:
- The AP15 Diesel Generator may be compact, but it packs a punch with its 15 KVA capacity. This makes it a practical and efficient choice for applications that require moderate yet reliable power.
- Fuel Efficiency:
- Powered by a fuel-efficient diesel engine, the AP15 ensures cost-effective operation. Its economical fuel consumption makes it an environmentally friendly and budget-conscious solution.
- Reliability in Small Packages:
- Despite its size, the AP15 is engineered for reliability. It incorporates quality components to ensure a stable power supply, even during outages or critical times.
- Versatile Application:
- The AP15 is adaptable to various environments and applications. It can serve as a primary power source for smaller facilities or as a backup power solution, making it an ideal choice for businesses and organizations with varying power needs.
- User-Friendly Controls:
- The generator is equipped with a user-friendly control panel that simplifies operation and monitoring, ensuring that you have full control of your power supply.
Applications
The AP15 Diesel Generator is suitable for a variety of applications, including:
- Small businesses and shops
- Construction sites
- Residential backup power
- Remote or off-grid locations
- Events and exhibitions
- Telecommunications towers
- Agriculture and farming operations
Maintenance
Regular maintenance is crucial to ensure optimal performance. Consider these maintenance tips for the AP15:
- Scheduled oil changes and filter replacements
- Routine checks of the cooling system
- Inspections of electrical connections
- Regularly test and exercise the generator
Safety Precautions
Safety is paramount when operating the AP15 generator. Follow these safety guidelines:
- Ensure proper ventilation to prevent exhaust buildup in the generator's vicinity.
- Regularly inspect and clean the generator and its surroundings.
- Ensure that operators are trained in the safe operation of the generator.
Conclusion
The AP15 Diesel Generator proves that compact size doesn't mean compromising on power. With its remarkable features, fuel efficiency, adaptability, and reliability, it represents a comprehensive power solution for businesses and organizations with diverse power needs. For the latest information on the AP15 and its specifications, consult with [Your Company] or an authorized distributor. Discover the convenience of compact yet robust power with the AP15.